| Parameter |
Unit |
Value |
| Product Model |
– |
OSFSZ20-360000/330 |
| Rated Capacity |
kVA |
360,000 (360/360/110 MVA) |
| Rated Voltage Ratio |
kV |
345±8×1.25%/115/35 |
| Short-Circuit Impedance |
% |
HV–MV: 10.5; HV–LV: 25; MV–LV: 13 |
| Rated Frequency |
Hz |
50 |
| Vector Group |
– |
YNa0d11 |
| Insulation Level |
kV |
HV: LI1175/AC510; MV: LI480/AC200; LV: LI200/AC85 |
| Cooling Method |
– |
ONAF |
| No-Load Loss |
kW |
≤87 |
| Load Loss |
kW |
≤668 (HV–MV, at 75°C) |
| Temperature Rise Limit |
K |
Top oil: 55 (corrected to 51 for altitude); Winding average: 65 (corrected to 61 for altitude); Winding hot-spot: 78 (corrected to 74 for altitude) |
| Noise (Sound Pressure Level) |
dB(A) |
≤68 (with forced-air cooling engaged, at 2 m) |
Is a 330kV Transformer Suitable for Your Project?
A 330 kV electrical transformer should be selected when the project grid or substation operates at the 330kV voltage level and requires voltage step-up or step-down between the transmission network and a lower-voltage system.
This three phase power transformer may be suitable for:
- 330kV transmission and receiving substations
- Regional power grid expansion projects
- Large photovoltaic and wind power stations
- Energy storage and hydrogen production projects
- Thermal, hydroelectric and other power plants
- Steel, mining, chemical and heavy industrial facilities
- High-capacity industrial substations
- Long-distance power transmission systems
The choice between a 220kV transformer , 330kV transformer or 500kV transformer should not be based only on transmission distance. Buyers should also consider the grid voltage, required capacity, short-circuit level, system connection scheme, expected load and local utility requirements.
Important Specifications to Confirm Before Ordering
For a 330kV ultra high voltage transformer, the correct technical configuration is more important than selecting a standard model from a catalogue. Before production, the following parameters should be confirmed.
| Item to Confirm |
Why It Matters |
| Rated capacity |
Determines whether the transformer can support the expected continuous and peak load |
| Voltage ratio |
Must match the high-, medium- and low-voltage sides of the power system |
| System frequency |
Normally specified as 50Hz or 60Hz according to the local grid |
| Number of windings |
Depends on whether the project requires two-winding, three-winding or autotransformer construction |
| Vector group |
Affects phase relationship, grounding and parallel operation |
| Short-circuit impedance |
Influences fault current, voltage regulation and parallel operation |
| Tap-changing method |
Determines whether voltage can be adjusted under load |
| Cooling method |
Must support the expected load profile and ambient conditions |
| Insulation level |
Must meet lightning impulse, switching impulse and power-frequency requirements |
| Loss limits |
Affect operating cost throughout the transformer service life |
| Noise limit |
Important for substations near residential or commercial areas |
| Installation conditions |
Altitude, temperature, pollution and seismic conditions can affect the final design |
Providing these details at the quotation stage helps the 330kV transformer manufacturer prepare a more accurate technical proposal and avoids repeated design changes later.
Custom 330kV Transformer Configuration
Liye can configure the 330kV transformer according to the customer’s system and project requirements. Available project-specific options may include:
- Customized rated capacity and voltage ratio
- Two-winding, three-winding or autotransformer configuration
- On-load tap changer configuration
- Customized impedance and loss requirements
- ONAN, ONAF or project-specified cooling arrangements
- High-altitude or high-temperature design
- Low-noise configuration
- Corrosion-resistant external coating
- Online temperature and dissolved-gas monitoring
- Remote communication and control interfaces
- Project-specific protection and alarm devices
- IEC, utility or customer-defined testing requirements
Customers can provide a transformer specification, single-line diagram or tender document for technical evaluation.
Request a 330kV Power Transformer Proposal
Looking for a reliable 330kV power transformer for a transmission substation, renewable energy plant or industrial power project? Send Liye your technical specification or single-line diagram. Our team will review the system requirements and provide a suitable transformer configuration, technical proposal and quotation.